Specification |
|
Power supply voltage |
AC100~240V 50/60Hz |
|
Voltage fluctuation
rang |
Power supply voltage
85~110% |
|
Voltage consumption |
10VA
(AC100V)~15VA(AC240V) approx. |
|
Input and indication
accuracy |
Thermocouple :
K,J,T,E,R,S |
|
R,S : Less than PV
value (±0.3% or ±3◦C : whichever is larger)
±1
digit |
|
Others: Less than PV
value (±0.3% or ±2◦C : whichever is larger)
±1
digit |
|
(But exclude error of
reference junction compensation from condition.) |
|
Pt 100, JPt100 |
|
Less than PV value
(±0.3% or ±0.8◦C : whichever is larger) ±1 digit |
|
Voltage: DC1~5V Current
: DC4 ~ 20mA/DCO~20mA |
|
Less than input range
±0.3%±1 digit |
|
Main Control Output |
Relay contact point
output : AC250V 3A (resistive load)
Voltage pulse output : DC 0/12
±15% more than
600Ω (resistive
load)
Current output : DC4~20mA less than 500Ω (resistive load) |
|
Sub control output |
NR2 : Same as Main
control output
NR4 : Relay contact point output : AC250V/1A (resistive load)
Voltage pulse output : DC
0/12V±15% more than 600Ω (resistive load) |
|
Alarm output1 |
Relay contact point
output : AC250V/1A (resistive load) |
|
Alarm output2 |
Same as Alarm output1
(NR4:Sub control output and Alarm output2 function are not useful
simultaneously) |
|
Display |
Digital display (LED)
Process value (PV) : red
Set value (SV : green |
|
Ambient temperature |
For use :
-10~50◦C
For storage : -25~65◦C |
|
Ambient humidity |
35~85% RH (Avoid
freezing or condensation) |
|
Environmental
conditions |
Installation category :
II
pollution degree : 2
Make sure the controller has 30 minutes or more for warm up |
|
Main Control output
relay life span |
Mechanical : more than
10,000,000 times
Electrical : more than 100,000 times |
|
Alarm output relay life
span |
Mechanical : more than
5,000,000 times
Electrical : more than 100,000 times |
|
Data backup |
Yes |